| Control Unit |
|
| Power Supply: |
115VAC or 230VAC 50/60Hz Std, 24VDC Opt
24Watts (Control unit only, not valves) |
| Alarm Outputs: |
(2) Relay Std (5A@240VAC Resistive, Form A SPST) |
| Analog Outputs: |
(2) 4-20mA Std (500Ohms Max, 100mA, 15VDC) |
| Inputs: |
(2) Relay and (2) 4-20mA Std, (4) 4-20mA Opt |
| Communications: |
(1) Modbus RTU, Modbus TCP or Ethernet IP Opt |
| Enclosure: |
NEMA 4X Aluminum Std Other Opt |
| Temperature: |
-13F to +160F (-25 to 70C) |
| User Interface: |
LCD with digital, analog & text display, 4 button keypad |
| Area Classification: |
Ordinary locations (CE Approved) Std, Hazardous areas Opt |
| General: |
Circuit boards conformal coated to protect from dust, moisture & corrosives |
| |
|
| Cleaning Control |
|
| Solenoid Outputs: |
8 Std, 16, 32, 48, 64, 80 or 96 Opt (600V/8A, 200VA per output max)
Solid state intelligent triac with protective snubber circuit |
| On Timing: |
16mSec to 2000mSec
Synchronized to AC line, Accuracy +/-1mSec, 16.67mSec increments |
| Off Timing: |
3Sec to 180Sec, Accuracy +/-0.5Sec, 1Sec increments |
| Modes: |
IntelliPULSE (Single and multi row), single cycle, cycle down etc Std
Programmable patter pulsing Opt
Multicompartment master control with online & offline cleaning, Opt |
| |
|
| Diagnostics |
1 Requires optional sensor |
| Solenoid Failure: |
Instant detection and row identification, Std |
| Diaphragm Failure1: |
Instant detection and row identification, Opt |
| Filter Leak Locating1: |
Row by row analysis and identification, Opt |
| |
|
| Sensors |
|
| Differential Pressure: |
0-10"WC, Model DP 20T Non-Clogging Transmitter Opt |
| Pulse Pressure: |
0-150PSI, Model SP 10T Opt |
| Particulate Sensor: |
10pA, 5.0pA or 0.5pA Resolution (0-1000pA Range) Opt
3, 5, 10, 15, 20, 30, 36" probe (Approximately 1/2 duct/pipe I.D.)
Extended nipples & rope sensors for large multicompartment baghouses |
| Other: |
Airflow, Fan amps, hopper level, temperature & more Opt |